XMTD-8000 Intelligent Temperature Regulator
General description :
8000 series intelligent(temperature) display regulator adopts large-scale integrated circuit. It has following features: high accuracy, strong seismic performance, high reliability, convenient installation, clear reading, no parallax, long-distance observation and so on. The product is widely used in many industries, such as: chemical industry, light industry, textile, metallurgy, clothing, heat treatment, fermentation, sugar, rubber vulcanization and so on, and it can measure the temperature at the range of -100xFF~+1600xFF and automatically control.
Product specification:
Input signal | K,E,J,S,B type thermocouple, Pt100, Cu50 type thermal resistance, standard voltage, resistance, current 0-10ma 4-20ma linear signal |
Accuracy | ±1%FS+1 digit or ±0.5%FS+1 digit |
Adjustment types | ON/OFF Two switches type, Intermittent PID, continuous PID |
Control output | Relay contact、triggers the SSR voltage signal, output DC4-20mA current, Single – bidirectional thyristor zero-crossing trigger pulse 、single – phase two-way thyristor phase – shift trigger pulse |
Alarm output | Relay contact |
Working power supply | AC220V±10% (50/60Hz) |
Size options:
Models |
External size (W x H x D) |
Hole size |
XMTG-8 □□□ |
48 x 48 x 110 (mm) |
45 x 45 (mm) |
XMTE-8 □□□ |
48 x 96 x 110 (mm) |
45 x 92 (mm) |
XMTD-8 □□□ |
72 x 72 x 110 (mm) |
68 x 68 (mm) |
XMTA-8 □□□ |
96 x 96 x 110 (mm) |
92 x 92 (mm) |
XMT-8 □□□ |
80 x 160 x 80 (mm) |
76 x 152 (mm) |
Remarks: the symbol ”□” represents what functions you need, please refer to the following explanation.
Model explanation:
XMT□-8 □ □ □
① ② ③ ④
① Dimensions: A:96×96 D:72×72 E:48×96 G:48×48
② Adjustments type:
0: two switches type 2: three switches type
4: Output electric shock continuous PID 5: Output trigger SSR Intermittent PID
6: Single phase phase shift continuous PID
7: Single phase zero – crossing triggering SCR intermittent PID
8: Three phase zero-crossing triggering SCR intermittent PID
9: Continuous PID adjustment(4-20mA)
③ Alarm types: 0: no alarm 1: upper absolute value alarm
2: lower absolute value alarm
3: upper and lower absolute value alarm
④ Distribution sensor type:
1: thermocouple 2: thermal resistance 3: standard current
4: resistance signal 5: current 0-10mA 6: current 4-20mA