General description :
CH series intelligent (temperature) display regulator adopts 8-bit single-chip
high reliability, a variety of sensors freely input, and it adopts a wide range of
switching power supply. The productβs performance indicators, input style, control
function and the installation size are fully compatible with the i mported intelligent
digital temperature controller. CH series intelligent meters, having the latest fuzzy
control and combining with advanced PID adjustment algorithm, precisely control
the controlled objects.
Size options:
Models |
External size (W x H x D) |
Hole size |
CH102 β‘β‘β‘-β‘β‘*β‘β‘-β‘ |
48 x 48 x 110 (mm) |
45 x 45 (mm) |
CH402 β‘β‘β‘-β‘β‘*β‘β‘-β‘ |
48 x 96 x 110 (mm) |
45 x 92 (mm) |
CH702 β‘β‘β‘-β‘β‘*β‘β‘-β‘ |
72 x 72 x 110 (mm) |
68 x 68 (mm) |
CH902 β‘β‘β‘-β‘β‘*β‘β‘-β‘ |
96 x 96 x 110 (mm) |
92 x 92 (mm) |
CH502 β‘β‘β‘-β‘β‘*β‘β‘-β‘ |
96 x 48 x 110 (mm) |
92 x 45 (mm) |
Remarks: the symbol ββ‘β represents what functions you need, please refer to the following explanation.
Model explanation:
CHβ‘02 β‘ β‘ β‘- β‘ β‘*β‘ β‘-β‘
β β‘ β’ β£ β€ β₯ β¦ β§ β¨
β Standard sizes: 1οΌ48x48x110mmοΌγ4οΌ48x96x110mmοΌγ
7οΌ72x72x110mmοΌγ9οΌ96x96x110mmοΌγ5οΌ96x48x110mmοΌ
β‘ Control style: F: PID action and automatic calculus(reverse action)
D: PID action and automatic calculus(positive action)
β’ Input style: thermocouple: K, J, R, S, B, E, T, N, W5Re/W26Re, PLII, U, L,
thermal resistance Pt100, JPt100
β£ Display range:
Input type |
Input display range |
Code |
γ |
Input type |
Input display range |
Code |
K |
0~200β |
K 01 |
γ |
S |
0~1600β |
S 01 |
0~400β |
K 02 |
γ |
0~1769β |
S 02 |
||
0~600β |
K 03 |
γ |
B |
400~1800β |
B 01 |
|
0~800β |
K 04 |
γ |
0~1820β |
B 02 |
||
0~1200β |
K 06 |
γ |
E |
0~800β |
E 01 |
|
J |
0~200β |
J 01 |
γ |
0~1000β |
E 02 |
|
0~400β |
J 02 |
γ |
J |
-199.90~+649.0β |
D 01 |
|
0~600β |
J 03 |
γ |
-199.90~+200.0β |
D 02 |
||
0~800β |
J 04 |
γ |
-100.0~+200.0β |
D 05 |
||
0~1200β |
J 06 |
γ |
0.0~+200.0β |
D 08 |
||
R |
0~1600β |
J 01 |
γ |
0.0~+500.0β |
D 10 |
β€ The first control output: (OUT1)(Heating side)
M: relay contact output 8: Current output(DC4-20mA)
V: voltage pulse output G: Thyristor control tube drive with trigger output
T: Thyristor control tube output
β₯ The second control output: (OUT2)(Cooling side)*2
No mark: when the control action is F or C
M: relay contact output 8: Current output(DC4-20mA)
V: voltage pulse output T: Thyristor control tube output
β¦ First alarm(ALAM1)
N: no alarm A: Upper limit deviation alarm
B: Lower limit deviation alarm C: Upper and lower limit deviation alarm
W: Lower-limit set alarm value H: Upper limit output value alarm
β§ Second alarm(ALAM)*2(Same content as the frist alarm)
J: Lower output value alarm V: Upper set value alarm
β¨ Communication function:
N: no communication function 5: RS-485(double cable system)